ASTM D6113-21 - 1.3.2021
 
Significance and Use

5.1This test method is used to determine the heat release rate and a number of other fire-test-response characteristics as a result of exposing insulating materials contained in electrical or optical cables to a prescribed initial test heat flux in the cone calorimeter apparatus.

5.2Quantitative heat release measurements provide information that is potentially useful for design of electrical or optical cables, and product development.

5.3Heat release measurements provide useful information for product development by giving a quantitative measure of specific changes in fire performance caused by component and composite modifications. Heat release data from this test method will not be predictive of product behavior if the product will not spread flame over its surface under the fire exposure conditions of interest.

5.4The fire-test-response characteristics determined by this test method are affected by the thickness of the material used as test specimen, whether as a plaque or as coating on a wire or cable. The diameter of the wire or cable used will also affect the test results.

5.5A radiant exposure is used as an energy source for this test method. This type of source has been used for comparison with heat release rate and flame spread studies of insulating materials constructed into cables when burning in a vertical cable tray configuration (Test Methods D5424 and D5537) (2-9). No definitive relationships have been established.

5.6The value of heat release rate corresponding to the critical limit between propagating cable fires and non-propagating fires is not known.

5.7This test method does not determine the net heat of combustion.

5.8It has not been demonstrated that this test method is capable of predicting the response of electrical or optical fiber cables in a full scale fire. In particular, this test method does not address the self-extinguishing characteristics of the cables in a full scale fire.

 
1. Scope

1.1This is a fire-test-response standard.

1.2Several fire-test-response characteristics, including the time to sustained flaming, heat release rate, total heat released, effective heat of combustion, and specific extinction area; are measured or calculated by this test method at a constant radiant heat flux. For specific limitations see also 5.7 and Section 6.

1.3The tests are conducted by burning the electrical insulating materials contained in electrical or optical fiber cables when the cable test specimens, excluding accessories, are subjected to radiant heat.

1.4The values stated in SI units are to be regarded as the standard. The values given in parentheses are for information only.

1.5This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. For specific precautionary statements, see Section 7.

1.6This standard measures and describes the response of materials, products, or assemblies to heat and flame under controlled conditions, but does not by itself incorporate all factors required for fire hazard or fire risk assessment of the materials, products or assemblies under actual fire conditions.

1.7Fire testing is inherently hazardous. Adequate safeguards for personnel and property shall be employed in conducting these tests.

1.8This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

 
2. Referenced Documents

D618-21

Standard Practice for Conditioning Plastics for Testing

IEC 60695-5-2

Fire Hazard Testing. Part 5: Assessment of Potential Corrosion Damage by Fire Effluent - Section 2: Guidance on the Selection and Use of Test Methods

D5537-23a

Standard Test Method for Heat Release, Flame Spread, Smoke Obscuration, and Mass Loss Testing of Insulating Materials Contained in Electrical or Optical Fiber Cables When Burning in a Vertical Cable Tray Configuration (Includes all amendments and changes 5/18/2023).

E176-24a

Standard Terminology of Fire Standards (Includes all amendments and changes 12/9/2024).

E691-23

Standard Practice for Conducting an Interlaboratory Study to Determine the Precision of a Test Method

E906-09

Standard Test Method for Heat and Visible Smoke Release Rates for Materials and Products Using a Thermopile Method

E1354-26

Standard Test Method for Heat and Visible Smoke Release Rates for Materials and Products Using an Oxygen Consumption Calorimeter

D1711-26

Standard Terminology Relating to Electrical Insulation

D5424-23a

Standard Test Method for Smoke Obscuration of Insulating Materials Contained in Electrical or Optical Fiber Cables When Burning in a Vertical Cable Tray Configuration (Includes all amendments and changes 5/18/2023).

E2965-25

Standard Test Method for Determination of Low Levels of Heat Release Rate for Materials and Products Using an Oxygen Consumption Calorimeter

C22.2 No. 0.3, FT4, Vertical Flame Tests: Cables in Cable Trays, Section 4.11.4 in C22.2 No. 0.3, Test Methods for Electrical Wires and Cables Available from Canadian Standards Association (CSA), 5060 Spectrum Way, Mississauga, ON L4W 5N6, Canada, http://www.csa.ca.

E1474-22

Standard Test Method for Determining the Heat Release Rate of Upholstered Furniture and Mattress Components or Composites Using a Bench Scale Oxygen Consumption Calorimeter

E2058-19

Standard Test Methods for Measurement of Material Flammability Using a Fire Propagation Apparatus (FPA)

IEEE 1202

Standard for Flame Testing of Cables for Use in Cable Tray in Industrial and Commercial Occupancies, IEEE Standard 1202 Available from Institute of Electrical and Electronics Engineers, Inc. (IEEE), 445 Hoes Ln., P.O. Box 1331, Piscataway, NJ 08854-1331, http://www.ieee.org.

IEC 60695-4

Fire Hazard Testing. Part 4: Terminology Concerning Fire Tests Available from International Electrotechnical Commission (IEC), 3 rue de Varemb, Case postale 131, CH-1211, Geneva 20, Switzerland, http://www.iec.ch.

D5485-26

Standard Test Method for Determining Corrosive Effect of Combustion Products Using the Cone Corrosimeter