ASTM D6504-11(2016)e1 - 15.2.2016
 
Significance and Use

5.1 Cation conductivity provides one of the most sensitive and dependable on-line means of detecting anionic contamination in the boiler/steam cycle, such as chlorides, sulfates, nitrates, bicarbonates, and organic acids, such as formic and acetic.

5.2 High sensitivity is provided by intentionally eliminating the pH adjusting treatment chemical(s), for example, ammonia and amines, from the sample and converting remaining salt contaminants into their acid forms which are approximately three times as conductive.

5.3 Guidelines on cation conductivity limits for various cycle chemistry and boiler types have been established by EPRI (2-4) and by ASME (5 and 6).

5.4 The sample effluent from the cation exchange column also may be used, and in some cases is preferred, for ion chromatography or other anion measurements.

 
1. Scope

1.1 This practice describes continuous sample conditioning by hydrogen ion exchange and measurement by electrolytic conductivity. It is commonly known as cation conductivity measurement in the power industry although it is actually an indication of anion contamination in high purity water samples. Measurements are typically in a range less than 1 μS/cm.

1.2 The actual conductivity measurements are made using Test Method D5391.

1.3 This practice does not provide for separate determination of dissolved carbon dioxide. Refer to Test Method D4519.

1.4 The values stated in SI units are to be regarded as standard. The values given in parentheses are mathematical conversions to inch-pound units that are provided for information only and are not considered standard.

1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

 
2. Referenced Documents

D3370-25

Standard Practices for Sampling Water from Flowing Process Streams

D1129-24

Standard Terminology Relating to Water

D1193-24

Standard Specification for Reagent Water

D5540-13(2021)

Standard Practice for Flow Control and Temperature Control for On-Line Water Sampling and Analysis

D3864-12(2021)

Standard Guide for On-Line Monitoring Systems for Water Analysis

D1125-23

Standard Test Methods for Electrical Conductivity and Resistivity of Water

D1066-18(2025)

Standard Practice for Sampling Steam

D5391-23

Standard Test Method for Electrical Conductivity and Resistivity of a Flowing High Purity Water Sample

D4519-25