ASTM D6513-00 - 10.2.2000
 
1. Scope

1.1 This practice covers procedures for calculating the superimposed axial load required to be applied to load-bearing wood-frame walls throughout standard fire-endurance and fire and hose-stream tests.

1.2 The calculations determine the maximum load allowed by design for wood-frame wall assemblies under nationally recognized structural design criteria.

1.3 This practice is only applicable to those wood-frame assemblies for which the nationally recognized structural design criteria is the National Design Specification for Wood Construction (NDS).

1.4 The system of units to be used is that of the nationally recognized structural design criteria. For the NDS, the units are inch-pound.

1.5 The text of this standard references notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.

This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

 
2. Referenced Documents

E1529-22

Standard Test Methods for Determining Effects of Large Hydrocarbon Pool Fires on Structural Members and Assemblies

NDS—National Design Specification for Wood Construction

E119-26

Standard Test Methods for Fire Tests of Building Construction and Materials

D9-20

Standard Terminology Relating to Wood and Wood-Based Products

E176-24a

Standard Terminology of Fire Standards (Includes all amendments and changes 12/9/2024).

NDS Supplement—Design Values for Wood Construction