ASTM D7297-21 - 1.9.2021
 
Significance and Use

5.1?IAQ-based complaints and problems include discomfort/medical symptoms and unacceptable indoor environmental conditions such as odors that exist in residential buildings. The frequency of the occurrence of IAQ complaints and problems may be unknown.

5.2?Characterization of IAQ concerns and identification of their underlying causes require systematic observations and measurements of the indoor air and environment, its occupants and potential contaminant sources. This practice provides background and procedures for the investigation of IAQ concerns.

5.3?Where the dwelling is not owner-occupied, formal permission to access certain areas of the property and to collect information essential to the IAQ investigation is often required.

5.4?The stepwise and phased approach described in this practice allows for an investigation that is commensurate with the nature of the problem and the level of resources available for the investigation.

 
1. Scope

1.1?This standard practice describes procedures for evaluating indoor air quality (IAQ) concerns in residential buildings.

1.2?The practice primarily addresses IAQ concerns encountered in single-family detached and attached (for example, townhouse or duplex design) residential buildings. Limited guidance is also provided for low- and high-rise multifamily dwellings, such as condominiums and apartments.

1.3?The IAQ evaluation procedures are comprised of interviews with the homeowner or resident(s) (including telephone interviews and face-to-face meetings) and on-site investigations (including walk-through, assessment, and measurements). For application practicality, these procedures are divided into three separate phases, which may occur over one or more site visits.

1.4?The procedures described in this standard practice are aimed at identifying potential causes contributing to an IAQ issue or concern. Such findings can be the basis for recommending corrective measures. This standard practice does not describe problem resolution or corrective measures, and the standard is not intended to evaluate the impact of corrective measures.

1.5?This practice describes a pathway for characterizing indoor air, though using this practice does not guarantee that an investigator will be able to identify or resolve an IAQ complaint for one or more of the following reasons: (1) the diversity of sources and contaminants in indoor air; (2) other factors that may affect occupant perception and acceptance of indoor air quality, such as air temperature, humidity, noise, lighting, and psychological stress; (3) the range of susceptibility in the population.

1.6?Implementation of procedures given in this standard requires the investigator (or investigative team) to have adequate background in several areas: general principles of IAQ; interviewing techniques; building design and construction practices; basic understanding of heating and cooling systems and appliances; use of IAQ measurement equipment; interpretation of IAQ data; and technical report writing.

1.7?Although many elements described in this standard practice may be useful in training of IAQ investigators, it should not be used as the sole basis for specifying or conducting such training.

1.8?This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use. For additional safety precautionary information, see Section 6.

1.9?This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

 
2. Referenced Documents

E741-24

Standard Test Method for Determining Air Change in a Single Zone by Means of a Tracer Gas Dilution

E1554-07

Standard Test Methods for Determining Air Leakage of Air Distribution Systems by Fan Pressurization

D5955-02

Standard Test Methods for Estimating Contribution of Environmental Tobacco Smoke to Respirable Suspended Particles Based on UVPM and FPM

D6333-23

Standard Practice for Collection of Dislodgeable Pesticide Residues from Floors

E620-18

Standard Practice for Reporting Opinions of Scientific or Technical Experts

E1186-22

Standard Practices for Air Leakage Site Detection in Building Envelopes and Air Barrier Systems

E1827-22

Standard Test Methods for Determining Airtightness of Buildings Using an Orifice Blower Door

E1998-25

Standard Guide for Assessing Depressurization-Induced Backdrafting and Spillage from Vented Combustion Appliances

E2128-20

Standard Guide for Evaluating Water Leakage of Building Walls

ASHRAE 62.2-2010

Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings Available from American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. (ASHRAE), 1791 Tullie Circle, NE, Atlanta, GA 30329, http://www.ashrae.org.

E779-19

Standard Test Method for Determining Air Leakage Rate by Fan Pressurization

E943-23

Standard Terminology Relating to Biological Effects and Environmental Fate

D5197-21

Standard Test Method for Determination of Formaldehyde and Other Carbonyl Compounds in Air (Active Sampler Methodology)

D5438-23

Standard Practice for Collection of Floor Dust for Chemical Analysis

D5466-21

Standard Test Method for Determination of Volatile Organic Compounds in Atmospheres (Canister Sampling, Mass Spectrometry Analysis Methodology)

D5952-08

Standard Guide for the Inspection of Water Systems for Legionella and the Investigation of Possible Outbreaks of Legionellosis (Legionnaires' Disease or Pontiac Fever)

D6196-23

Standard Practice for Choosing Sorbents, Sampling Parameters and Thermal Desorption Analytical Conditions for Monitoring Volatile Organic Chemicals in Air

D6271-10

Standard Test Method for Estimating Contribution of Environmental Tobacco Smoke to Respirable Suspended Particles Based on Solanesol

D6345-10

Standard Guide for Selection of Methods for Active, Integrative Sampling of Volatile Organic Compounds in Air (Withdrawn 2018)

E241-20

Standard Guide for Limiting Water-Induced Damage to Buildings

E609-25

Standard Terminology Relating to Pesticides

D1356-20a

Standard Terminology Relating to Sampling and Analysis of Atmospheres (Includes all amendments and changes 9/7/2020).

D1357-26

Standard Practice for Planning the Sampling of the Ambient Atmosphere

D4861-23

Standard Practice for Sampling and Selection of Analytical Techniques for Pesticides and Polychlorinated Biphenyls in Air