Significance and Use

This specification applies to products that are used in buildings. While products that comply with this specification are used in various constructions, they are adaptable primarily, but not exclusively, to wood frame construction.

Since the property of thermal resistance for a specific thickness of blanket is only part of the total thermal performance of a building element such as a wall, ceiling, floor, and so forth, this specification states only general classifications for thermal resistance of the fibrous blanket itself. Facings that provide additional resistance to water-vapor transfer can affect system performance.

 
1. Scope

1.1 This specification covers the composition and physical properties of mineral-fiber blanket insulation used to thermally or acoustically insulate ceilings, floors, and walls in light frame construction and manufactured housing. The requirements cover fibrous blankets and facings. Values for water-vapor permeance of facings are suggested for information that will be helpful to designers and installers.

1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.

1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

 
2. Referenced Documents

C1304-23

Standard Test Method for Assessing the Odor Emission of Thermal Insulation Materials

C1338-25

Standard Test Method for Determining Fungi Resistance of Insulation Materials and Facings

C1104/C1104M-19(2025)

Standard Test Method for Determining the Water Vapor Sorption of Unfaced Mineral Fiber Insulation

G1-25

Standard Practice for Preparing, Cleaning, and Evaluating Corrosion Test Specimens

E970-25

Standard Test Method for Critical Radiant Flux of Exposed Attic Floor Insulation Using a Radiant Heat Energy Source

E96/E96M-24a

Standard Test Methods for Gravimetric Determination of Water Vapor Transmission Rate of Materials (Includes all amendments and changes 11/20/2024).

E84-26a

Standard Test Method for Surface Burning Characteristics of Building Materials (Includes all amendments and changes 4/15/2026).

C1617-24

Standard Test Method for Quantitative Accelerated Laboratory Evaluation of Extraction Solutions Containing Ions Leached from Thermal Insulation on Aqueous Corrosion of Carbon Steel

C653-24

Standard Guide for Determination of the Thermal Resistance of Low-Density Blanket-Type Mineral Fiber Insulation

C518-21

Standard Test Method for Steady-State Thermal Transmission Properties by Means of the Heat Flow Meter Apparatus

C390-08(2024)

Standard Practice for Sampling and Acceptance of Thermal Insulation Lots

C177-19(2026)

Standard Test Method for Steady-State Heat Flux Measurements and Thermal Transmission Properties by Means of the Guarded-Hot-Plate Apparatus

C168-25

Standard Terminology Relating to Thermal Insulation

C167-25

Standard Test Methods for Thickness and Density of Blanket or Batt Thermal Insulations

B152/B152M-24

Standard Specification for Copper Sheet, Strip, Plate, and Rolled Bar