ASTM E2322-03(2015) - 1.3.2015
 
Significance and Use

4.1 Transverse Load—The procedures outlined will serve to evaluate the performance of floor and roof segments for deflection, permanent set and ultimate capacity. Performance criteria based on data from these procedures can ensure structural adequacy and effective service.

4.2 Concentrated Load—This concentrated load test shall be used to evaluate surface indentation of structural framing members.

4.3 These procedures will serve to evaluate performance of roof and floor segments under simulated service conditions. Diaphragm shear loading of roof and floor segments shall be evaluated under Test Method E455. Impact loading shall be evaluated under Test Methods E661 or E695.

 
1. Scope

1.1 This test method covers the following procedures for determining the structural properties of segments of floor and roof constructions:

 

 

Section

 

Test Specimens

5

 

Loading

6

 

Deformation Measurements

7

 

Report

8

 

Precision and Bias

9

 

 Testing Floors

 

 

Transverse Load

10

 

Concentrated Load

11

 

 Testing Roofs

 

 

Transverse Load

12

 

Concentrated Load

13

1.2 This test method serves to evaluate the performance of floors and roofs panels subjected to (1) Uniform loading, and (2) Concentrated static loading, which represent conditions sustained in the actual performance of the element. The standard is not intended for the evaluation of individual structural framing or supporting members (floor joist, rafters, and trusses), or both.

1.3 The text of this standard references notes and footnotes which provide explanatory material. These notes and footnotes, excluding those in tables and figures, shall not be considered as requirements of the standard.

1.4 This standard is not intended to cover concrete floor slabs.

1.5 The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard.

1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

 
2. Referenced Documents

E196-06(2018)

Standard Practice for Gravity Load Testing of Floors and Low Slope Roofs

E455-19

Standard Test Method for Static Load Testing of Framed Floor or Roof Diaphragm Constructions for Buildings

E695-22

Standard Test Method of Measuring Relative Resistance of Wall, Floor, and Roof Construction to Impact Loading

E661-22

Standard Test Method for Performance of Wood and Wood-Based Floor and Roof Sheathing Under Concentrated Static and Impact Loads

E1592-05(2017)

Standard Test Method for Structural Performance of Sheet Metal Roof and Siding Systems by Uniform Static Air Pressure Difference

E631-15

Standard Terminology of Building Constructions

E575-05(2018)

Standard Practice for Reporting Data from Structural Tests of Building Constructions, Elements, Connections, and Assemblies

E73-13(2021)

Standard Practice for Static Load Testing of Truss Assemblies

E72-22

Standard Test Methods of Conducting Strength Tests of Panels for Building Construction

E4-21

Standard Practices for Force Calibration and Verification of Testing Machines

C109/C109M-23

Standard Test Method for Compressive Strength of Hydraulic Cement Mortars (Using 50?mm [2 in.] Cube Specimens)