ASTM E2751/E2751M-17 - 1.1.2017
 
Significance and Use

4.1 Glass is a brittle material with different time and temperature-dependent properties than other solid materials used as walkways surfaces. Therefore, the type of glass is an important consideration in the design and construction of glass treads and glass landings constructed with laminated glass.

4.2 Post-breakage glass retention is an important consideration in the design of a glass walkway system as a means of minimizing tripping, cutting/piercing injuries, or fall-through or fallout of the glass.

4.3 The structural design shall be confirmed by calculations by a licensed design professional in accordance with Section 5.

4.4 If testing is required (see 4.4.1 – 4.4.3) to verify post-glass breakage behavior of the glass walkway, the testing shall be in accordance with Section 6.

4.4.1 For laminates with two glass plies, verification testing is required.

4.4.2 For laminates with more than two glass plies, verification testing is not required provided that calculations completed in accordance with 4.3 demonstrate that the glass assembly has sufficient strength to sustain the full design load with any one glass ply broken.

4.4.3 When verifying post-breakage behavior by calculation, allowable glass stress for 10 min load duration in accordance with Table 1 shall be used for all load cases.

4.5 The manufacturer or designer of glass walkway systems shall provide installation directions and fabrication and installation tolerances of their systems.

4.6 The structural integrity of the glass walkway system after glass breakage shall be sufficient to support the design loads after any one glass ply is broken. If damage of any kind occurs, the walkway shall be cordoned off and the installation shall be inspected to ensure structural integrity and pedestrian safety of the system.

 
1. Scope

1.1 This practice addresses elements related to load-bearing glass walkways, glass treads, and glass landings constructed with laminated glass. This standard includes performance, design, and safe behavior considerations. It addresses the characteristics unique to glass and laminated glass. Issues that are common to all walkways, such as slip resistance, are addressed in existing referenced standards.

1.2 This practice does not address glass walkways constructed with monolithic glass, glass block, insulating glass units, glass tiles that are directly bonded to a non-glass structural substrate, or glass walkways intended to support vehicular traffic.

1.3 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in each system may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from the two systems may result in non-conformance with the standard.

1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

 
2. Referenced Documents

C1048-18

Standard Specification for Heat-Strengthened and Fully Tempered Flat Glass

C1036-21

Standard Specification for Flat Glass

ANSI/ASSE TR-A1264.3-2007

ANSI Technical Report, Using Variable Angle Tribometers (VAT) for Measurement of the Slip Resistance of Walkway Surfaces

F609-05(2013):2013/ADJF0609

Adjunct to F609 Test Method for Using a Horizontal Pull Slipmeter (HPS)

E1300-16

Standard Practice for Determining Load Resistance of Glass in Buildings

C1028-07

Standard Test Method for Determining the Static Coefficient of Friction of Ceramic Tile and Other Like Surfaces by the Horizontal Dynamometer Pull-Meter Method

C1172-19

Standard Specification for Laminated Architectural Flat Glass

E631-15

Standard Terminology of Building Constructions