ASTM G158-98(2016) - 1.5.2016
 
Significance and Use

4.1 This guide provides three methods for determining the suitability of a buried steel tank to be upgraded with cathodic protection.

4.2 This guide may be used to assess any UST, including non-regulated USTs.

4.3 This guide provides three alternative methods but does not recommend any specific method or application. The responsibility for selection of a method rests with the user.

4.4 This guide has specific requirements for vendor provided information which should be requested and reviewed by the user.

 
1. Scope

1.1 This guide covers procedures to be implemented prior to the application of cathodic protection for evaluating the suitability of a tank for upgrading by cathodic protection alone.

1.2 Three procedures are described and identified as Methods A, B, and C.

1.2.1 Method A—Noninvasive with primary emphasis on statistical and electrochemical analysis of external site environment corrosion data.

1.2.2 Method B—Invasive ultrasonic thickness testing with external corrosion evaluation.

1.2.3 Method C—Invasive permanently recorded visual inspection and evaluation including external corrosion assessment.

1.3 This guide presents the methodology and the procedures utilizing site and tank specific data for determining a tank's condition and the suitability for such tanks to be upgraded with cathodic protection.

1.4 The tank's condition shall be assessed using Method A, B, or C. Prior to assessing the tank, a preliminary site survey shall be performed pursuant to Section 8 and the tank shall be tightness tested pursuant to 5.2 to establish that the tank is not leaking.

1.5 While this guide provides minimum procedures for assessing a tank's condition, this guide does not provide minimum installation procedures or requirements for upgrades of the tank by cathodic protection.

1.6 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.

1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

 
2. Referenced Documents

RP-0169

Standard Recommended Practice-Control on External Corrosion on Underground or Submerged Metallic Piping Systems

G57-20

Standard Test Method for Measurement of Soil Resistivity Using the Wenner Four-Electrode Method

E1526-93

Standard Practice for Evaluating the Performance of Release Detection Systems for Underground Storage Tank Systems (Withdrawn 2002)

E1323-15(2020)

Standard Guide for Evaluating Laboratory Measurement Practices and the Statistical Analysis of the Resulting Data

D2216-19

Standard Test Methods for Laboratory Determination of Water (Moisture) Content of Soil and Rock by Mass

RP-0187

E797-05

Standard Practice for Measuring Thickness by Manual Ultrasonic Pulse-Echo Contact Method

G51-23

Standard Test Method for Measuring pH of Soil for Use in Corrosion Evaluations

ASNT SNT-TC-1A

RP-0285

Standard Recommended Practice-Corrosion Control of Underground Storage Tank Systems by Cathodic Protection

E114-20

Standard Practice for Ultrasonic Pulse-Echo Straight-Beam Contact Testing